Function library

Torque (torque control)

Setting of motor control

12

l

359

EDBCSXS064 EN 4.0

12.28.4.6

Field weakening

(

Stop!

The available torque is reduced by the field weakening.

The motor is operated in the field weakening range if

ƒ

the output voltage of the controller exceeds the rated motor voltage (C0090).

ƒ

The controller is no longer able to increase the output voltage with rising speed due
to the mains voltage or DC−bus voltage.

)

Note!

An optimal machine operation in the field weakening range requires a correct
setting of the field controller and field weakening controller (

^ 157).

Manual field weakening

(

Stop!

If the field is weakened manually (TORQUE−MCTRL.FldWeak
(C7531/6) < 100 %), the drive cannot create the maximum torque.

A manual field weakening is possible via TORQUE−MCTRL.FldWeak (7531/6).

ƒ

For a maximum excitation, TORQUE−MCTRL.FldWeak must be triggered with +100 %
(= 16384).

ƒ

If TORQUE−MCTRL.FldWeak is not assigned (free), the field weakening automatically
amounts to +100 %.