Appendix – Lenze ECSCSxxx User Manual

Page 393

Advertising
background image

Appendix

Code table

13

l

393

EDBCSXS064 EN 4.0

IMPORTANT

Possible settings

Code

Selection

Lenze/
{Appl.}

Designation

No.

C0595 MONIT CE4

3

Fault response − system bus
(CAN) monitoring "Bus−off" at X4
"BusOffState" (CE4)

^ 198

0

TRIP

2

Warning

3

Off

C0596 NMAX limit

5500

Maximum system speed

^ 223

0

{1 rpm}

16000

C0597 MONIT LP1

3

Fault response − monitoring of
motor phase failure (LP1)
When this function is activated,
the calculating time provided for
the user program is reduced!

^ 217

0

TRIP

2

Warning

3

Off

C0598 MONIT SD5

3

Fault response − master current
monitoring at X6 < 2 mA
"MastISourceDef"

0

TRIP

2

Warning

3

Off

C0599 Limit LP1

5.0

Monitoring limit for motor phase
failure monitoring (LP1) with
regard to the current limit.

^ 217

0.01

{0.01 %}

10.00

C0602 MONIT REL1

3

Fault response − open circuit
monitoring of relay output X25

0

TRIP

2

Message

3

Off

4

FAIL−QSP

C0603 MONIT CE5

3

Fault response − gateway
function monitoring (CE5)
"Timeout" when remote
parameter setting (C0370) is
activated via interface X4 (CAN)

^ 198

^ 190

0

TRIP

2

Warning

3

Off

C0604 MONIT OC7

2

Fault response − monitoring of
Ixt device utilisation.
Ixt threshold can be set under
C0123.

^ 201

0

TRIP

2

Warning

3

Off

Advertising
This manual is related to the following products: