Monitoring functions

Configuring monitoring functions
Monitoring of the rotor position adjustment (PL)

9

l

224

EDBCSXS064 EN 4.0

9.3.20

Monitoring of the rotor position adjustment (PL)

Fault message

Monitoring function

System variable

Possible response

TRIP

Messag

e

Warnin

g

Off

089

PL

Fault during rotor position
adjustment

MCTRL_bRotorPositionFault_b

·

· Default setting

üSetting possible

This monitoring function observes the correct execution of the rotor position adjustment.

This monitoring function can occur during rotor position adjustment in connection with
feedback systems:

ƒ

Resolver

ƒ

TTL encoder

ƒ

Sin/cos encoder

ƒ

Absolute value encoder (single/multi−turn)

Cause for this is a cancellation of the adjustment routine as a result of

ƒ

a supply voltage loss

ƒ

an encoder cable interruption

ƒ

a routine stop through the deactivation of C0095

Reset fault message

1. Remove the cause for the cancellation.

2. Inhibit controller

3. Deactivate rotor position adjustment with C0095 = 0.

4. Carry out TRIP−RESET.

5. Activate rotor position adjustment with C0095 = 1.