Monitoring functions

Configuring monitoring functions

Monitoring times for process data input objects

9

l

199

EDBCSXS064 EN 4.0

IMPORTANT

Possible settings

Code

Selection

Lenze/
{Appl.}

Designation

No.

C2457

Monitoring time for
CANaux1...3_IN (CAN bus
interface X14)

^ 198

1 CE monit time

3000

1

{1 ms}

65000 CE11 monitoring time

2 CE monit time

3000

CE12 monitoring time

3 CE monit time

3000

CE13 monitoring time

The following responses can be set for communication errors:

ƒ

0 = Error (TRIP) − controller sets controller inhibit (CINH)

ƒ

2 = Warning

ƒ

3 = Monitoring is switched off

Codes for setting the response to the monitoring functions:

CAN bus interface

Code

Monitoring

X4

ECSxS/P/M: MotionBus (CAN)
ECSxA: System bus (CAN)

C0591

CAN1_IN ("CE1")

C0592

CAN2_IN ("CE2")

C0593

CAN3_IN ("CE3")

C0595

Bus off ("CE4")

C0603

Gateway function ("CE5")

X14

System bus (CAN)

C2481

CANaux1_IN ("CE11")

C2482

CANaux2_IN ("CE12")

C2483

CANaux3_IN ("CE13")

C2484

Bus off ("CE14")

C2485

Gateway function ("CE15")

The input signals (CAN1...3_IN/CANaux1...3_IN) can also be used as binary output signals,
e.g. for the assignment of the output terminal.

Bus off

If the controller disconnects from the CAN bus due to faulty telegrams, the signal
"BusOffState" (CE4/CE14) is set.

"BusOffState" can activate an error (TRIP) or warning. The signal can also be switched off.
The response is set under C0595/C2484. You can also assign the terminal output for this.