Configuration – Lenze ECSCSxxx User Manual
Page 174
![background image](/manuals/566263/174/background.png)
Configuration
Configuring MotionBus/system bus (CAN)
Individual addressing
l
174
EDBCSXS064 EN 4.0
IMPORTANT
Possible settings
Code
Selection
Lenze/
{Appl.}
Designation
No.
C0354
Alternative node address for
CAN_IN/CAN_OUT (CAN bus
interface X4)
^ 173
1 CAN addr.
129
1
{1}
512 Address 2 CAN1_IN
2 CAN addr.
1
Address 2 CAN1_OUT
3 CAN addr.
257
Address 2 CAN2_IN
4 CAN addr.
258
Address 2 CAN2_OUT
5 CAN addr.
385
Address 2 CAN3_IN
6 CAN addr.
386
Address 2 CAN3_OUT
Save changes with C0003 = 1.
The settings are only accepted after carrying out one of the following actions:
ƒ
Renewed switch−on of the 24 V low−voltage supply
ƒ
Reset node via the bus system (by the network management (NMT))
ƒ
Reset node with C0358 = 1
)
Note!
If reset node is executed via GDC, communication will be interrupted. You
therefore have to log in again manually or find the devices connected to the
bus once again (fieldbus scan).