Electrical installation

Control terminals
Analog input

5

l

70

EDBCSXS064 EN 4.0

5.3.2

Analog input

AI-

AG

AI+

GND

82k5

X6

=

=

82k5

250R

X3

5

6

3.3 nF

3.3 nF

"

"

ECSXA015

Fig. 5−10

Analog input at X6

"

HF−shield termination by large−surface connection to functional earth (see Mounting
Instructions for ECSZS000X0B shield mounting kit)

Analog input configuration

ƒ

Use C0034 to set whether the input is to be used for a master voltage (

±10 V) or a

master current (+4 ... 20 mA or

±20 mA).

ƒ

Set jumper bar X3 according to the setting in C0034:

(

Stop!

Do not plug the jumper on the pins 3−4! The axis module cannot be initialised
like this.

Jumper bar X3

Setting

Measuring range

6
4
2

5
3

1

5−6 open

Jumper on 1−2: Parking position

C0034 = 0 (master voltage)

l

Level: −10 ... +10 V

l

Resolution: 5 mV (11 bits + sign)

l

Scaling:

±10 V º ±16384 º ±100 %

6
4
2

5
3

1

5−6 closed

C0034 = 1 (master current)

l

Level: +4 ... +20 mA

l

Resolution: 20

mA (10 bits without sign)

l

Scaling:

+4 mA º 0 º 0 %

+20 mA º 16384 º 100 %

C0034 = 2 (master current)

l

Level: −20 ... +20 mA

l

Resolution: 20

mA (10 bits + sign)

l

Scaling:

±20 mA º ±16384 º ±100 %