Monitoring functions

Configuring monitoring functions

Voltage supply monitoring − control electronics (U15)

9

l

217

EDBCSXS064 EN 4.0

9.3.12

Voltage supply monitoring − control electronics (U15)

If the voltage at X6/DI1 or X6/DI3 falls below 17 V, TRIP "U15" is triggered. The fault can
only be reset if U > 19 V.

9.3.13

Motor phase failure monitoring (LP1)

Fault message

Monitoring function

System variable

Possible response

TRIP

Messag

e

Warnin

g

Off

032

LP1

Motor phase failure

MCTRL_bMotorphaseFail_b

ь

ь

·

· Default setting

üSetting possible

This monitoring function checks whether a motor phase has failed.

)

Note!

ƒ

This monitoring function can only be used for asynchronous motors.

ƒ

When this monitoring function is activated, the calculating time available to
the user is reduced.

ƒ

The response is set via C0597.

ƒ

The monitoring limit is set via C0599.

Reset fault message

1. Check motor cables.

2. Carry out TRIP−RESET.

Code

Possible settings

IMPORTANT

No.

Designation

Lenze/
{Appl.}

Selection

C0597 MONIT LP1

3

Fault response − monitoring of
motor phase failure (LP1)
When this function is activated,
the calculating time provided for
the user program is reduced!

^ 217

0

TRIP

2

Warning

3

Off

C0599 Limit LP1

5.0

Monitoring limit for motor phase
failure monitoring (LP1) with
regard to the current limit.

^ 217

0.01

{0.01 %}

10.00