Appendix

Code table

13

l

377

EDBCSXS064 EN 4.0

IMPORTANT

Possible settings

Code

Selection

Lenze/
{Appl.}

Designation

No.

C0173 UG limit

11

Adaptation of the DC−bus
voltage thresholds:

l

Check during commissioning
and adapt, if necessary.

l

All drive components in DC
bus connections must have
the same thresholds.
– LU = Undervoltage

threshold

– OU = Overvoltage threshold

^ 98

0

Mains = 230 V

± B

Operation on 230 V mains with
or without brake unit
LU = 130 V, OU = 400 V

1

Mains = 400 V

± B

Operation on 400 V mains with
or without brake unit
LU = 285 V, OU = 800 V

2

Mains = 460 V

± B

Operation on 460 V mains with
or without brake unit
LU = 328 V, OU = 800 V

3

Mains = 480V − B

Operation on 480 V mains
without brake unit
LU = 342 V, OU = 800 V

4

Mains = 480V + B

Operation on 480 V mains with
brake unit
LU = 342 V, OU = 800 V

10

Mains = 230 V

± B

Operation on 230 V mains with
or without brake unit
LU = C0174, OU = 400 V

11

Mains = 400 V

± B

Operation on 400 V mains with
or without brake unit
LU = C0174, OU = 800 V

12

Mains = 460 V

± B

Operation on 460 V mains with
or without brake unit
LU = C0174, OU = 800 V

13

Mains = 480V − B

Operation on 480 V mains
without brake unit
LU = C0174, OU = 800 V

14

Mains = 480V + B

Operation on 480 V mains with
brake unit
LU = C0174, OU = 800 V

C0174 UG min

60

Undervoltage threshold of DC
bus (LU)

^ 98

15

{1 V}

342

C0175 UG−Relais Fkt

1

Charge relay behaviour with
undervoltage (LU) in the DC bus.

^ 98

1

Standard

Relay switches as a function of
LU.

2

One Time

Relay switches when LU is
exceeded for the first time and
remains on.

3

Fixed On

Charging current limitation is
inactive.

l

Relay is always switched on
and the charging resistors of
the axis module are thus
permanently jumpered.

l

Setting for operation with
ECSxE power supply module.