Appendix – Lenze ECSCSxxx User Manual

Page 391

Advertising
background image

Appendix

Code table

13

l

391

EDBCSXS064 EN 4.0

IMPORTANT

Possible settings

Code

Selection

Lenze/
{Appl.}

Designation

No.

C0576 nErr tolerance

100

Tolerance window for the speed
system deviation referring to
n

max

100 % = lowest monitoring
sensitivity

^ 222

0

{1 %}

100

C0577 Vp fld weak

0.100

Gain of the field weakening
controller (V

p

)

^ 157

0.000

{0.001}

63.999

C0578 Tn fld weak

3.0

Integral−action time of the field
weakening controller (V

n

)

0.1

{0.1 ms}

6000.0

C0579 nErr response

3

Fault response − monitoring of
speed system deviation

^ 222

0

TRIP

1

Message

2

Warning

3

Off

4

FAIL−QSP

C0580 Monit SD8

3

Fault response − monitoring of
SinCos signals at X8

^ 221

0

TRIP

3

Off

C0581 MONIT EEr

0

Fault response − external fault
monitoring "ExternalFault" (EEr)

^ 298

0

TRIP

1

Message

2

Warning

3

Off

4

FAIL−QSP

C0582 MONIT OH4

2

Setting of the fault response −
monitoring of heatsink
temperature in C0122

^ 204

0

TRIP

2

Warning

3

Off

C0583 MONIT OH3

0

Fault response − monitoring of
motor temperature (fixed
temperature threshold).
Detection through KTY thermal
sensor via resolver input X7 or
encoder input X8.

^ 202

0

TRIP

2

Warning

3

Off