Appendix

Code table

13

l

394

EDBCSXS064 EN 4.0

IMPORTANT

Possible settings

Code

Selection

Lenze/
{Appl.}

Designation

No.

C0605 MONIT OH5

2

Fault response − monitoring of
temperature inside the
controller.
Temperature threshold can be
set under C0124.

^ 205

0

TRIP

2

Warning

3

Off

C0606 MONIT OC8

2

Fault response − monitoring of
I

2

x t motor utilisation.

Threshold can be set under
C0120.

^ 210

0

TRIP

2

Warning

3

Off

C0607 MONIT NMAX

0

Fault response − maximum speed
monitoring of the machine

0

TRIP

2

Warning

3

Off

C0608 ovr. Tx−Queue

2

Fault response − transmission
memory overflow of free CAN
objects

0

TRIP

1

Message

2

Warning

3

Off

4

FAIL−QSP

C0745

Only the Lenze service is allowed
to make changes!
Oscilloscope − internal service

C0746

Only the Lenze service is allowed
to make changes!
Oscilloscope − internal service

1

...

24

C0747

Only the Lenze service is allowed
to make changes!
Oscilloscope − internal service

C0855

Digital process data input words
are indicated on the AIF interface
(AIF1_IN)
Hexadecimal value is bit−coded.
Read only

^ 248

1 AIF1 IN bits

0000

{hex}

FFFF Input word 2 (bit 0 ... 15)

2 AIF1 IN bits

Input word 3 (bit 0 ... 15)