Monitoring functions

Configuring monitoring functions

DC−bus voltage monitoring (OU, LU)

9

l

215

EDBCSXS064 EN 4.0

Switch−off and switch−on thresholds

ƒ

The switch−off threshold defines the voltage level of the DC−bus voltage, at which
the pulse inhibit is activated.

ƒ

The switch−off and switch−on thresholds dependent on C0173 can be gathered from
the following table:

Selection

Mains voltage

Brake unit

LU message

(Undervoltage)

OU message

(Overvoltage)

C0173

Power supply module

[V AC]

Setting

[V DC]

Resetting

[V DC]

Setting

[V DC]

Resetting

[V DC]

0

230

yes/no

130

275

400

390

1

400

yes/no

285

430

800

790

2

400 ... 460

yes/no

328

473

800

790

3

480

no

342

487

800

785

4

480

yes

342

487

800

785

10

230

yes/no

C0174

C0174 + 5 V

400

390

11

400 (Lenze setting)

yes/no

C0174

C0174 + 5 V

800

790

12

400 ... 460

yes/no

C0174

C0174 + 5 V

800

790

13

480

no

C0174

C0174 + 5 V

800

785

14

480

yes

C0174

C0174 + 5 V

800

785

I

Tip!

If undervoltage is existent for more that 3 s, or if mains connection is carried
out, an entry into the fault memory is effected.

ƒ

This operational mode can occur if the control module is fed via the
terminals X6/+24 and X6/GND by means of an external supply and the
mains are disconnected.

ƒ

If there is no undervoltage anymore (mains are reconnected again), the
entry in the fault memory is not continued, but deleted. This case does not
describe an error, but a state of the drive controller.

Undervoltages of less than 3 s are interpreted as a fault (e. g. mains fault) and
are entered into the fault memory. In this case, the fault memory is updated.