Appendix, Code table – Lenze ECSCSxxx User Manual

Page 372

Advertising
background image

Appendix

Code table

13

l

372

EDBCSXS064 EN 4.0

IMPORTANT

Possible settings

Code

Selection

Lenze/
{Appl.}

Designation

No.

C0124 OH5 limit

75

Threshold for temperature
monitoring inside the device

^ 205

10

{1 %}

90 C0062 > C0124

ð fault message

OH5 (C0605)

C0125 Baud rate

0

Baud rate for operation via AIF
interface X1

0

9600 bit/s

Communication modules on AIF
interface X1:

l

LECOM−A/B/LI 2102

l

PROFIBUS−DP 2133

1

4800 bits/s

2

2400 bit/s

3

1200 bit/s

4

19200 bit/s

C0126 MONIT CE0

3

Fault response regarding the
monitoring of communication
via AIF interface X1.

l

Via C2382 you can select
whether controller inhibit
(CINH) or quick stop (QSP) is
activated when a CE0 fault
occurs.

^ 247

0

TRIP

A communication error activates
the CE0 response set.

2

Warning

3

Off

Monitoring switched off.

C0127 OC8 limit

100

Threshold for I

2

x t warning

(motor)

^ 210

0

{1 %}

120 I

2

x t > C0127

ð fault message

OC8 (C0606)

C0128 Tau motor

5.0

Thermal time constant of the
motor

^ 210

0.5

{0.1 min}

25.0 For calculating the I

2

x t

disconnection

C0129 Charc.: Ix/Nx

Reduction of the speed/torque
characteristic for UL−compliant
thermal motor monitoring (I

2

x t)

The reduced speed/torque
characteristic reduces the
permissible thermal load of
self−ventilated standard motors.

^ 25

1

100

10

{1 %}

200 S1 torque characteristic I

1

/I

rated

This value also enables an
increase of the maximally
permissible utilisation.

2

40

S1 torque characteristics
n

2

/n

rated

With increasing speeds, the
maximally permissible
utilisation remains unchanged
(I

Mot

= I

rated

).