12 function library, 1 aif (automation interface management), Function library – Lenze ECSCSxxx User Manual

Page 247: Aif (automation interface management), Response to ce0 communication error

Advertising
background image

Function library

AIF (Automation interface management)

12

l

247

EDBCSXS064 EN 4.0

12

Function library

12.1

AIF (Automation interface management)

Function

This function block serves to monitor communication faults by means of a fieldbus module
connected to the automation interface (AIF).

ƒ

If a fault occurs, the monitoring sets "AIF−Ce0CommErr" to TRUE and releases the
communication error CE0 (LECOM No. 61); the corresponding response can be
configured via C0126 (default setting: Off).

ƒ

When using more current AIF fieldbus modules (e.g. EMF2133IB and EMF2175IB), a
fault number is output in addition from the fieldbus module via the
"AIF−FieldBusStateBit0 ...7".

,

Please read the documentation for the connected fieldbus module.

AIF

AIF

Communication

Error

AIF

Fieldbus State

10

11

12

13

14

15

16

17

18

AIF-Ce0CommErr

AIF-FieldBusStateBit0

AIF-FieldBusStateBit1

AIF-FieldBusStateBit2

AIF-FieldBusStateBit6

AIF-FieldBusStateBit5

AIF-FieldBusStateBit4

AIF-FieldBusStateBit3

AIF-FieldBusStateBit7

X1

ECSXA200

Fig. 12−1

AIF function block

Response to CE0 communication error

Code

Possible settings

IMPORTANT

No.

Designation

Lenze/
{Appl.}

Selection

C0126 MONIT CE0

3

Fault response regarding the
monitoring of communication
via AIF interface X1.

l

Via C2382 you can select
whether controller inhibit
(CINH) or quick stop (QSP) is
activated when a CE0 fault
occurs.

^ 247

0

TRIP

A communication error activates
the CE0 response set.

2

Warning

3

Off

Monitoring switched off.