Troubleshooting and fault elimination, Fault messages causes and remedies – Lenze ECSCSxxx User Manual

Page 241

Advertising
background image

Troubleshooting and fault elimination

Fault messages

Causes and remedies

11

l

241

EDBCSXS064 EN 4.0

Remedy

Cause

Description

Fault message

Remedy

Cause

Description

Display

No.

0074

PEr

Program error

Error in the program flow

l

Check use of pointers.

l

Send module with PLC
program and parameter set to
Lenze (on floppy
disk/CD−ROM).

0075

PR0

Error in parameter set.

The operating system software
has been updated.

Storage of the Lenze setting
C0003 = 1.

After troubleshooting: Deenergise
the device completely (disconnect
24 V supply, discharge DC bus)!

0076

PR5

Memory error

Error saving parameters in the
fail−safe memory area.

Contact Lenze

0079

PI

Fault during parameter
initialisation

l

An error has been detected
during parameter set transfer
between two controllers.

l

Parameter set does not match
the controller, e.g. when data
were transmitted from a
controller with more
performance to a controller
with less performance.

l

Correct parameter set.

l

Check code initialisation
values.

After fault correction: completely
deenergise the device (switch off
24 V supply, discharge DC bus)!

0080

PR6

With ECSxS/P/M: internal error

Contact Lenze.

With ECSxA: too many user codes

Reduce number of user codes.

x082

Sd2

Resolver error at X7

Resolver cable is interrupted.

l

Check cable for wire breakage.

l

Check resolver.

l

Switch off monitoring
(C0586 = 3).

Excitation amplitude is too low.

Increase excitation amplitude of
resolver (C0416).
Check control factor of resolver
under C0414 (as of operating
system V8.0).

x085

Sd5

Master current value encoder
error at analog input X6/AI+, AI−
(C0034 = 1)

Master current value at
X6/AI+, AI− < 2mA

l

Check cable for wire breakage.

l

Check master current value
encoder.

l

Switch off monitoring
(C0598 = 3).

l

Check control factor of resolver
under C0414 (as of operating
system V8.0).

x086

Sd6

Motor temperature sensor error
(X7 or X8)

Encoder for detecting the motor
temperature at X7 or X8 indicates
undefined values.

l

Check cable for firm
connection.

l

Switch off the monitoring
(C0594 = 3).

x: 0 = TRIP, 1 = Message, 2 = Warning, 3 = FAIL−QSP