12.27.4.1

Closing holding brake

A HIGH level on the input SPEED−BRK.SetBrake (C7411/10 = TRUE) activates the function.
At the same time, the output SPEED−BRK.SetQSP is set to HIGH. This signal can be used to
brake the drive to standstill via a deceleration ramp (speed = 0).

If the setpoint speed falls below the value set at the input SPEED−BRK.SpeedThreshold
(C7431/9), the output SPEED−BRK.Out is set to HIGH.

)

Note!

For a fail−safe design this signal must be inverted at the output (e. g. via
C0118).

After the brake closing time set C0195 has lapsed, the output SPEED−BRK.SetCInh switches
to TRUE. By means of this signal you can for example activate controller inhibit
(device−internal on the function block DCTRL). The setting of the brake closing time is
required because the brake is not immediately activated at SPEED−BRK.Out = TRUE (the
drive has to provide another holding torque for the set time).

t

t

t

t

t

0

1



‚

ƒ

„

…

ECSXASA002

Fig. 12−31

Signal characteristic − closing of holding brake



SPEED−BRK.SetBrake

‚

SPEED−BRK.SetQSP

ƒ

SPEED−BRK.MSetOut

„

SPEED−BRK.Out

…

SPEED−BRK.SetCInh

0

SPEED−BRK.SpeedThreshold

1

Brake closing time (C0195)