2 setting the voltage thresholds, Setting the voltage thresholds, Commissioning – Lenze ECSCSxxx User Manual

Page 99

Advertising
background image

Commissioning

Setting of mains data

Setting the voltage thresholds

6

l

99

EDBCSXS064 EN 4.0

Code

Possible settings

IMPORTANT

No.

Designation

Lenze/
{Appl.}

Selection

C0175 UG−Relais Fkt

1

Charge relay behaviour with
undervoltage (LU) in the DC bus.

^ 98

1

Standard

Relay switches as a function of
LU.

2

One Time

Relay switches when LU is
exceeded for the first time and
remains on.

3

Fixed On

Charging current limitation is
inactive.

l

Relay is always switched on
and the charging resistors of
the axis module are thus
permanently jumpered.

l

Setting for operation with
ECSxE power supply module.

6.5.2

Setting the voltage thresholds

)

Note!

All drive components in DC−bus connections must have the same thresholds!

Selection

Mains voltage

Brake unit

LU message

(Undervoltage)

OU message

(Overvoltage)

C0173

Power supply module

[V AC]

Setting

[V DC]

Resetting

[V DC]

Setting

[V DC]

Resetting

[V DC]

0

230

yes/no

130

275

400

390

1

400

yes/no

285

430

800

790

2

400 ... 460

yes/no

328

473

800

790

3

480

no

342

487

800

785

4

480

yes

342

487

800

785

10

230

yes/no

C0174

C0174 + 5 V

400

390

11

400 (Lenze setting)

yes/no

C0174

C0174 + 5 V

800

790

12

400 ... 460

yes/no

C0174

C0174 + 5 V

800

790

13

480

no

C0174

C0174 + 5 V

800

785

14

480

yes

C0174

C0174 + 5 V

800

785

Code

Possible settings

IMPORTANT

No.

Designation

Lenze/
{Appl.}

Selection

C0174 UG min

60

Undervoltage threshold of DC
bus (LU)

^ 98

15

{1 V}

342