Function library

SYS

12

l

317

EDBCSXS064 EN 4.0

12.26

SYS

Function

This function block contains global system variables which are firmly integrated into the
run−time system. They provide functions for programming relief.

ƒ

On the function block outputs clock signals with the same pulse/pause ratio are
output.

ƒ

The outputs are toggled in real time.

ƒ

If you use these output signals, observe the scanning frequency at which the
outputs are scanned (Aliasing effect). It should at least be twice the toggle
frequency.

The following outputs are integrated:

Output

Toggle frequency

Period

Clock01Hz

0.1 Hz

T = 10 s

Clock1Hz

1.0 Hz

T = 1 s

Clock10Hz

10 Hz

T = 100 ms

Clock0100Hz

100 Hz

T = 10 ms

SYS

880

881

882

883

Clock01Hz

Clock1Hz

Clock10Hz

Clock100Hz

ECSXA263

Fig. 12−27

SYS function block