Electrical installation, Stop – Lenze ECSCSxxx User Manual

Page 75

Advertising
background image

Electrical installation

Control terminals

Safe torque off

5

l

75

EDBCSXS064 EN 4.0

5.3.3.5

Function check

ƒ

After installation the operator must check the "safe torque off" function.

ƒ

The function check must be repeated at regular intervals, after one year at the
latest.

(

Stop!

If the function check leads to impermissible states at the terminals,
commissioning cannot take place!

Test specifications

ƒ

Check the circuitry with regard to correct function.

ƒ

Check directly at the terminals whether the "safe torque off" function operates
faultlessly in the axis module:

States of the "safe torque off" function on the axis module

Level at input terminal

Resulting level at

output terminal

Impermissible level at

output terminal

X6/SI1

X6/SI2

X6/SO

X6/SO

LOW

LOW

HIGH

LOW

LOW

HIGH

LOW

HIGH

HIGH

LOW

LOW

HIGH

HIGH

LOW

Advertising
This manual is related to the following products: