Monitoring functions – Lenze ECSCSxxx User Manual

Page 216

Advertising
background image

Monitoring functions

Configuring monitoring functions
DC−bus voltage monitoring (OU, LU)

9

l

216

EDBCSXS064 EN 4.0

Code

Possible settings

IMPORTANT

No.

Designation

Lenze/
{Appl.}

Selection

C0173 UG limit

11

Adaptation of the DC−bus
voltage thresholds:

l

Check during commissioning
and adapt, if necessary.

l

All drive components in DC
bus connections must have
the same thresholds.
– LU = Undervoltage

threshold

– OU = Overvoltage threshold

^ 98

0

Mains = 230 V

± B

Operation on 230 V mains with
or without brake unit
LU = 130 V, OU = 400 V

1

Mains = 400 V

± B

Operation on 400 V mains with
or without brake unit
LU = 285 V, OU = 800 V

2

Mains = 460 V

± B

Operation on 460 V mains with
or without brake unit
LU = 328 V, OU = 800 V

3

Mains = 480V − B

Operation on 480 V mains
without brake unit
LU = 342 V, OU = 800 V

4

Mains = 480V + B

Operation on 480 V mains with
brake unit
LU = 342 V, OU = 800 V

10

Mains = 230 V

± B

Operation on 230 V mains with
or without brake unit
LU = C0174, OU = 400 V

11

Mains = 400 V

± B

Operation on 400 V mains with
or without brake unit
LU = C0174, OU = 800 V

12

Mains = 460 V

± B

Operation on 460 V mains with
or without brake unit
LU = C0174, OU = 800 V

13

Mains = 480V − B

Operation on 480 V mains
without brake unit
LU = C0174, OU = 800 V

14

Mains = 480V + B

Operation on 480 V mains with
brake unit
LU = C0174, OU = 800 V

C0174 UG min

60

Undervoltage threshold of DC
bus (LU)

^ 98

15

{1 V}

342