Configuration

Configuring MotionBus/system bus (CAN)

Setting of boot−up time/cycle time

8

l

177

EDBCSXS064 EN 4.0

Code

Possible settings

IMPORTANT

No.

Designation

Lenze/
{Appl.}

Selection

C0356

CAN time settings for CAN bus
interface X4

^ 176

1 CAN times

3000

0

{1 ms}

65000 CAN boot−up time:

Delay time after mains
connection for initialisation
through the master.

2 CAN times

0

CAN2...3_OUT cycle times:
Factor for the task time to send
process data telegram.
0 = event−controlled
transmission

3 CAN times

0

4 CAN times

20

Delay time for initial
transmission of the process data
objects 2 and 3 after the CAN bus
changed to "Operational"

Save changes with C0003 = 1.

The settings are only accepted after carrying out one of the following actions:

ƒ

Renewed switch−on of the 24 V low−voltage supply

ƒ

Reset node via the bus system (by the network management (NMT))

ƒ

Reset node with C0358 = 1

)

Note!

If reset node is executed via GDC, communication will be interrupted. You
therefore have to log in again manually or find the devices connected to the
bus once again (fieldbus scan).