24 inneg, Function library, Inneg – Lenze ECSCSxxx User Manual

Page 313: Codes

Advertising
background image

Function library

InNeg

12

l

313

EDBCSXS064 EN 4.0

12.24

InNeg

Function

This function block serves to invert the input signals. The function block can invert digital,
analog and phase signals.

ƒ

The values of the analog signals are in a decimal range of ±32767.

ƒ

The values of the phase signals are in a decimal range of ±2147483648.

The values are calculated before the selected main function block is calculated. Thus the
calculated values are made available to the subsequent blocks in the current cycle.

InNeg

C7130/1

32767

-32767

-1

C7130/2

32767

-32767

-1

C7150/1

2147483647

-2147483647

-1

C7110/1

-1

C7110/2

-1

C7110/3

-1

C7150/2

2147483647

-2147483647

-1

C7131/1

C7131/2

C7111/1

C7111/2

C7111/3

C7151/1

C7151/2

651

652

651

652

653

651

652

InNeg-AnIn1

InNeg-AnIn2

InNeg-PhiIn1

InNeg-DigIn1

InNeg-DigIn2

InNeg-DigIn3

InNeg-PhiIn2

InNeg-AnOut1

InNeg-AnOut2

InNeg-PhiOut1

InNeg-DigOut1

InNeg-DigOut2

InNeg-DigOut3

InNeg-PhiOut2

ECSXA251

Fig. 12−25

InNeg function block

Codes

Code

Possible settings

IMPORTANT

No.

Designation

Lenze/
{Appl.}

Selection

C7110

Display of the digital input
signals in the function block
InNeg (signal inversion)

^ 313

1 InNeg−digV

InNeg−DigIn1

2 InNeg−digV

InNeg−DigIn2

3 InNeg−digV

InNeg−DigIn3

C7111

Selection of the digital input
signals for the InNeg function
block (signal inversion)

^ 313

1 InNeg−dig

1000

0 (FALSE, not assigned)

Source for InNeg−DigIn1

2 InNeg−dig

1000

0 (FALSE, not assigned)

Source for InNeg−DigIn2

3 InNeg−dig

1000

0 (FALSE, not assigned)

Source for InNeg−DigIn3

For possible signals see "selection list − digital
signals"

^ 428

Advertising