Electrical installation

Wiring of system bus (CAN)

5

l

85

EDBCSXS064 EN 4.0

Example: Selection help

Specifications

l

Cable cross−section:

0.5 mm

2

(according to cable specifications

^ 82)

l

Number of nodes:

63

l

Repeater:

Lenze−repeater, type 2176 (cable reduction: 30 m)

For the max. number of nodes (63), the following cable lengths / number of repeaters from
the specifications must be observed:

Baud rate [kbit/s]

50

120

250

500

1000

Max. cable length [m]

1500

630

290

120

25

Segment cable length [m]

310

310

290

120

25

Number of repeaters

5

2

Check repeater application

Given:

l

Baud rate:

125 kbps

l

Cable cross−section:

0.5 mm

2

l

Number of nodes:

28

l

Cable length:

450 m

Procedure

Cable length

See

1. Total cable length at 125 kbps:

630 m

Tab. 5−1

2. Segment cable length for 28 bus nodes and a cable cross−section of

0.5 mm

2

:

360 m

Tab. 5−2

3. Comparison: The value under point 2 is smaller than the required cable length of 450 m.

Conclusion

l

It is not possible to use a cable length of 450 m without using a repeater.

l

After 360 m (point 2) a repeater must be installed.

Result

l

The Lenze repeater type 2176 is used (cable reduction: 30 m)

l

Calculation of the maximum cable length:
First segment: 360 m
Second segment: 360 m (according to Tab. 5−1) minus 30 m (cable reduction when a repeater is used)

à

Maximum possible cable length with repeater: 690 m.

à

Now it is possible to use the required cable length.

)

Note!

Repeaters are recommended as a

ƒ

Service interface
Advantage: Trouble−free connecting during bus operation is possible.

ƒ

Calibration interface
Advantage: Calibration/programming unit remains electrically isolated.