Monitoring functions – Lenze ECSCSxxx User Manual

Page 210

Advertising
background image

Monitoring functions

Configuring monitoring functions
Current load of motor (I

2

x t monitoring: OC6, OC8)

9

l

210

EDBCSXS064 EN 4.0

9.3.10

Current load of motor (I

2

x t monitoring: OC6, OC8)

)

Note!

ƒ

I

2

x t monitoring is based on a mathematical model which calculates a

thermal motor load from the detected motor currents.

ƒ

The calculated motor load is saved when the mains is switched.

ƒ

The function is UL−certified, i.e. no additional protective measures are
required for the motor in UL−approved systems.

ƒ

However, I

2

x t monitoring is no full motor protection as other influences on

the motor load could not be detected as for instance changed cooling
conditions (e.g. interrupted or too warm cooling air flow).

Die I

2

x t load of the motor is displayed in C0066.

The thermal loading capacity of the motor is expressed by the thermal motor time
constant (

t, C0128). Find the value in the rated motor data or contact the manufacturer of

the motor.

The I

2

x t monitoring has been designed such that it will be activated after 179 s in the

event of a motor with a thermal motor time constant of 5 minutes (Lenze setting C0128),
a motor current of 1.5 x I

N

and a trigger threshold of 100 %.

Two adjustable trigger thresholds provide for different responses.

ƒ

Adjustable response OC8 (TRIP, warning, off).
– The trigger threshold is set in C0127.
– The response is set in C0606.
– The response OC8, for instance, can be used for an advance warning.

ƒ

Fixed response OC6−TRIP.
– The trigger threshold is set in C0120.

Behaviour of the I

2

x t monitoring

Condition

The I

2

x t monitoring is deactivated.

C0066 is set = 0 % and
MCTRL−LOAD−I2XT is set = 0.00 %.

When C0120 = 0 % and C0127 = 0 %, set controller
inhibit.

I

2

x t monitoring is stopped.

The current value in C0066 and at the
MCTRL−LOAD−I2XT output is frozen.

When C0120 = 0 % and C0127 = 0 %, set controller
enable.

I

2

x t monitoring is deactivated.

The motor load is displayed in C0066.

Set C0606 = 3 (off) and C0127 > 0 %.

)

Note!

An error message OC6 or OC8 can only be reset if the I

2

x t load falls below the

set trigger threshold by 5 %.

Advertising
This manual is related to the following products: