35 gmde, 35�1 gmde – Solare Datensysteme Solar-Log User Manual

Page 114

Advertising
background image

114

GMDE

GMDE

35 GMDE

35�1 GMDE

Easy Installation

Termination

Addressing

Interface

No

Yes

No

RS485

Overview

Integrated RS485 interface

8-pin cable for the RS485 connection of the Solar-Log™

Communication address does not have to be assigned

Installation steps

Switch off the inverters and Solar-Log™

Connect inverters to the Solar-Log™

Connect the inverters to each other

Connect inverters to the Solar-Log™

The wiring is done using a

partially ready-made RJ45 cable (not included)

or

self-made data cable with RJ45 plug and 6-pin terminal block connector

Caution

Risk of damage to the unit!
The Solar-Log™ also has an RJ45 socket, which must never be connected to the RJ45
socket on the inverter.

Only connect inverters via the RS485/422 Solar-Log™ interface(s).

Procedure

1.

Connect wires as shown in the diagram:

Solar-Log™ terminal strip connector

RJ45 inverter

Terminal

PIN

► 1 (Data+) A

► 3 A

► 4 (Data-) B

► 6 B

2. Run the wire from the Solar-Log™ to inverter 1 through the hole for the wire on the bottom of the unit.

3. In the inverter insert the RJ45 plug into the "RS-485 out" socket.

4. Insert the terminal block connector into the Solar-Log™ RS485 socket.