47 kyocera inverter/battery system, 47�1 kyocera inverter/battery system – Solare Datensysteme Solar-Log User Manual

Page 146

Advertising
background image

146

Kyocera Inverter/Battery System

Kyocera Inverter/Battery System

47 Kyocera Inverter/Battery System

47�1 Kyocera Inverter/Battery System

Easy Installation

Termination

Addressing

Interface

No

No

Yes

RS485

Selections available under Kyocera

Overview

Integrated interface.

Where to connect: Terminal strip under the cover on the bottom.

The communication address has to be assigned.

2-pin wiring

Installation steps

Switch off the inverters and Solar-Log™.

Connect inverters to the Solar-Log™.

Connect the inverters/battery systems to each other.

Assign the communication address according to the manufacturer‘s manual.

Connect the inverters to the Solar-Log™�

The wiring is done using a

self-made, shielded 4-wire data cable with a terminal block connector.

Procedure

1.

Unscrew the side cover as shown in the inverter‘s instructions.

2. If you are making the cable yourself, connect the wires as shown in the following diagram:

Solar-Log™ terminal strip connector

Inverter terminal strip

Terminal

PIN

► 1 Data+

► 3 Data+

► 4 Data-

► 4 Data-

3. Screw the inverter cover on again.

4. Insert the terminal block connector into the Solar-Log™ RS485 socket.

Connect the inverters to each other�

Where to connect: Terminal strip under the cover on the bottom.

Procedure

1.

Unscrew the side cover as shown in the inverter‘s instructions.

2. Connect the self-made RS-485 cable to the terminal block on inverter 1.

3. Connect other end of the self-made RS-485 cable to the terminal block on inverter 2 or to the battery

system.

4. Connect the other inverters to each other in the same way.

5. Screw the inverter cover on again.