Solare Datensysteme Solar-Log User Manual

Page 184

Advertising
background image

184

REFUSOL

REFUSOL

Connect the inverters to each other

Connect using
– 2-wire, shielded data cable and
– 4-pin "SACC-M12MS-4SC" plug (two plugs included with the inverter)

Where to connect: RS485 sockets on the bottom of the inverter.

The RS485 IN and OUT sockets are each double connections so that the wiring can be continued to the

next inverter.

Procedure

1.

Connect the data cable to the "SACC-M12MS-4SC" plug as shown in the inverter's instructions.

2. Insert one plug into the OUT (X14B) socket of inverter 1.

3. Insert the other end of the wire into the IN socket (X15B) on inverter 2.

4. Connect the other inverters to each other in the same way.

5. Terminate in the last inverter.

On the sockets "RS485 OUT" with REFUSOL round plugs bypass the connections PIN1 to PIN2 and

PIN3 to PIN4.

6. Close inverters.

Allocate communication address

Recommendation: Continuous numbering starting with 1; highest possible address: 31

Set the following parameters on the inverter's operating display:

1.

Press "F1", select

Numerical list

, press "ENTER".

2. Set parameter number

2000

[password protection],

press "ENTER" twice.

3. Enter

72555

, press "ENTER"

4. Set parameter number

0406

, press "ENTER"

5. Select sub parameter

0406,3

, press "ENTER"

6. Enter figure for communication

x

[x = continuous numbering starting with 1; highest possible address: 31], press "ENTER". 31], press

"ENTER".

After configuring on the display:

1.

Using the installed DC isolating switch turn the inverters on and off briefly so that the settings are

activated.

2. Set the date and time on the inverter as shown in the inverter instructions.

Older Solar-Log™ / Refusol installations: Set compatibility

With older Solar-Log™ / Refusol installations the inverter had to be set with additional parameters for

Solar-Log™ compatibility. This is only still necessary if an inverter has been replaced because it was faulty

or if the system is extended. In these cases the new inverters must also be provided with the extended

parameters again.

The extended parameters are only available starting from inverter firmware version 800.2.20 or higher. The

firmware version can be checked on the inverter menu:

► "F1" /

Numerical list

/ Parameters 1.1 to 1.3

Current firmware versions and update instructions can be found at

www.refu-elektronik.de

.

Advertising