79�3 solarmax – e series – Solare Datensysteme Solar-Log User Manual

Page 241

Advertising
background image

241

SolarMax

SolarMax – E series

79�3 SolarMax – E series

Easy Installation

Termination

Addressing

Interface

Yes

No

Yes

RS485

Overview

Interface not integrated; Retrofit RS485 interface card.

6-pin wiring

Communication address must be allocated.

Installation steps

Switch off the inverters and Solar-Log™

Install the RS485 interface in the inverter

Connect inverters to the Solar-Log™

Connect the inverters to each other

Allocate communication address

Installing the RS485 interface
Procedure

► Install the RS485 interface in the inverter in accordance with the interface card installation instructions.

Connect inverters to the Solar-Log™

The wiring is done using a

ready-made data cable (optional extra; not supplied)

or

self-made cable connection using RS485 data cable, RJ45 plug and terminal block connector.

Caution

Risk of damage to the unit!
The Solar-Log™ also has an RJ45 socket, which must never be connected to the RJ45
socket on the inverter.

Only connect inverters via the RS485/422 Solar-Log™ interface(s).

Procedure

1.

Open the inverter as shown in the inverter's instructions.

2. If you are making the cable yourself, connect the wires as shown in the following diagram:

Solar-Log™ terminal strip connector

RJ45 inverter

Terminal

PIN

► 1

► 7

► 2

► 1

► 2

► 2

► 3

► 3

► 3

► 4

5 - unused

6 - unused

► 4

► 8