Solare Datensysteme Solar-Log User Manual

Page 276

Advertising
background image

276

Sunways

Sunways - AT/NT/PT

Connect the inverters to each other

Connect using a 2 wire, shielded data cable

Where to connect: Terminal strip inside the inverter

-

750 V models: 4 RS485 terminals on 10 pin terminal strip

-

850 V models: 4 pin RS485 terminal strip

The RS485 connections on the terminal strip are each double connections so that the wiring can be con-

tinued to the next inverter.

Procedure

1.

Open the inverter as shown in the inverter's instructions.

2. Connect terminals RS485+ and RS485- on all inverters to the two data cable wires in accordance with

the inverter instructions.

3. Terminate in the last inverter in accordance with the inverter instructions.

4. Close inverters.

Allocate communication address

Recommendation: Continuous numbering starting with 1.

Setting: Using the inverter operating display

Procedure: Start according to the inverter's instructions