Hyundai HPC-050HT-E and HPC-100HT-E

41 Hyundai

41�1 Hyundai HPC-050HT-E and HPC-100HT-E

Easy Installation

Termination

Addressing

Interface

No

Yes

Yes

RS485

Overview

Integrated interface

Where to connect: RJ45 CN socket on the outside of the inverter.

2-pin wiring

Communication address must be allocated.

Installation steps

Switch off the inverters and Solar-Log™

Connect inverters to the Solar-Log™

Connect the inverters to each other

Allocate communication address

Connect inverters to the Solar-Log™

The wiring is done using a

ready-made data cable (optional extra; not supplied)

or

self-made cable connection with RS485 data cable and terminal block connector.

Caution

Risk of damage to the unit!
The Solar-Log™ also has an RJ45 socket, which must never be connected to the RJ45
socket on the inverter.

Only connect inverters via the RS485/422 Solar-Log™ interface(s).

Procedure

1.

If you are making the cable yourself, connect the wires as shown in the following diagram:

Solar-Log™ terminal strip connector

RJ45 inverter

Terminal

PIN

► 1

► 3

► 4

► 6

2. Insert RJ45 plug into socket CN on the inverter.

3. If only one inverter is to be connected terminate this in accordance with the inverter instructions.

4. Insert the terminal block connector into the Solar-Log™ RS485 socket.