Solare Datensysteme Solar-Log User Manual

Page 179

Advertising
background image

179

PVPowered

PV Powered – central inverter RS485

Connect the inverters to each other

The wiring is done using a

self-made connection cable and terminal block connector.

Where to connect: Terminal strip inside the inverter

Procedure

1.

Open the inverter as shown in the inverter's instructions.

2. Pull the free wires through the wire opening in the inverter.

3. If you are making the cable yourself, connect the wires as shown in the following diagram

Solar-Log™ terminal strip connector

RJ45 inverter

Terminal

PIN

► 1

2 - D+

► 3

1 - GND

► 4

3 - D-

4. Connect terminals GND, D+ and D- of inverter 1 to the corresponding terminals on inverter 2.

5. Connect the other inverters to each other in the same way.

6. Terminate in the last inverter in accordance with the manufacturer's specifications.

Inside the inverter set the supplied jumper from "J4" to "J5"

7. Address the individual inverters in accordance with the manufacturer's handbook: Inverter 1 should be

the inverter that is directly connected to the Solar-Log™. To this end, set SW1 to "0". Depending on the

position of the inverter in the bus, SW2 should be set to 1-9.

If more than 9 inverters are to be connected to one Solar-Log™, please read the manufacturer's inst-

ructions for further information.

8. Close the inverter if no other inverters are to be connected.

9. Insert the terminal block connector into the Solar-Log™ RS485 socket.