Solare Datensysteme Solar-Log User Manual

Page 28

Advertising
background image

28

Advanced Energy

Advanced Energy - AE-3

On the sockets „RS485 OUT“ with REFUSOL round plugs bypass the connections PIN1 to PIN2 and

PIN3 to PIN4.

6. Close inverters.

Allocate communication address

Recommendation: Continuous numbering starting with 1; highest possible address: 31

Set the following parameters on the inverter‘s operating display:

1.

Press „F1“, select

Numerical list

, press „ENTER“.

2. Set parameter number

2000

[password protection],

press „ENTER“ twice.

3. Enter

72555

, press „ENTER“

4. Set parameter number

0406

, press „ENTER“

5. Select sub parameter

0406,3

, press „ENTER“

6. Enter figure for communication

x

[x = continuous numbering starting with 1; highest possible address: 31], press „ENTER“. 31], press

„ENTER“.

After configuring on the display:

1.

Using the installed DC isolating switch turn the inverters on and off briefly so that the settings are

activated.

2. Set the date and time on the inverter as shown in the inverter instructions.

Allocate communication address

Recommendation: Continuous numbering starting with 1.

Setting: Using the inverter operating display

Procedure: Start according to the inverter‘s instructions

Note

To use active and reactive power management, all of the inverters need to be set to:

Protocol 1

57600 baud

Parameter 1164 = 2