78 solaredge – Solare Datensysteme Solar-Log User Manual

Page 234

Advertising
background image

234

SolarEdge

SolarEdge

78 SolarEdge

78�1 SolarEdge

Easy Installation

Termination

Addressing

Interface

No

Switch

No

RS485

Overview

Integrated interface

Where to connect: Terminal strip inside the inverter

Communication address must be allocated.

3-pin wiring

Installation steps

Switch off the inverters and Solar-Log™

Connect inverters to the Solar-Log™

Address inverter and set protocol

Connect the inverters to each other

Note

Installing a “SolarEdge-Gateway” on a RS485 bus, connecting SolarEdge inverters with a
Solar-Log™, can lead to communication problems with the inverters. In order to ensure a
correct communication with the Solar-Log™, the “Wireless package” switch must be activ-
ated on the respective I/O port in the web menu.

=> The SolarEdge-Gateway is not supported on I/O port “C”, which has no wireless pack-
age option.

Connect inverters to the Solar-Log™

The wiring is done using a

self-made cable connection with terminal block connector.