Lufft - Pyranometer

Lufft - Pyranometer

48 Lufft - Pyranometer

48�1 Lufft - Pyranometer

Easy Installation

Termination

Addressing

Interface

No

-

No*

RS485

Selections available under Lufft

Overview

Integrated interface.

Where to connect: Round socket on the bottom.

Communication address does not have to be assigned.*

4-pin wiring

Installation steps

Switch off the pyranometer and the Solar-Log™.

Connect the pyranometer to the Solar-Log™.

Connect the pyranometer to the Solar-Log 1000, 1200 or 2000�

The wiring is done using a

self-made, shielded 4-wire data cable with a terminal block connector.

Procedure

1.

If you are making the cable yourself, connect the wires as shown in the following diagram:

Solar-Log™ terminal strip connector

X4 socket RS485-1 pyranometer

Terminal

PIN

► 1

► RS485 A (green)

► 2

► Positive voltage supply (brown)

► 3

► Ground (GND) (white)

► 4

► RS485 B (yellow)

*Allocate communication address:

The communication address is set to 1 by default. If several pyranometers are connected on a single bus,

the address has to be adjusted. This requires a tool from the company Lufft. It can be downloaded from

the Lufft website.

Termination

:

Please contact Lufft for information on termination.