82 solutronic – Solare Datensysteme Solar-Log User Manual

Page 252

Advertising
background image

252

Solutronic

Solutronic SP25-55 (RS485)

82 Solutronic

82�1 Solutronic SP25-55 (RS485)

Easy Installation

Termination

Addressing

Interface

No

Yes

Yes

RS485

Overview

Integrated interface

Where to connect: Terminal strip on the outside of the inverter

3-pin wiring

Communication address must be allocated.

All inverters must be fitted with firmware version 1.2.39 or later.

Inverters must be grounded otherwise this could lead to problems with inverter detection.

Installation steps

Switch off the inverters and Solar-Log™

Connect inverters to the Solar-Log™

Connect the inverters to each other

Allocate communication address

Connect inverters to the Solar-Log™

The wiring is done using a

ready-made data cable (optional extra; not supplied)

or

self-made, shielded 3 wire data cable and terminal block connector.

Procedure

1.

If you are making the cable yourself, connect the wires as shown in the following diagram:

Solar-Log™ terminal strip connector

Inverter terminal strip

Terminal

Terminal

► 1

► Pin 1 RS485-A

► 3

► Pin 3 GND

► 4

► Pin 2 RS485-B

2. If only one inverter is to be connected it must be terminated.

You will find detailed instructions for setting the inverters on the Solutronic website.

3. Close the inverter if no other inverters are to be connected.

4. Insert the terminal block connector into the Solar-Log™ RS485 socket.

Connect the inverters to each other

Connect using a 3 wire, shielded data cable

Where to connect: Terminal strip on the outside of the inverter