Solare Datensysteme Solar-Log User Manual

Page 175

Advertising
background image

175

Power-One/Aurora

Power-One/Aurora

Procedure

1.

Open the inverter as shown in the inverter's instructions.

2. Connect terminals +T/R, -T/R and RTN of inverter 1 to the corresponding terminals on inverter 2.

3. Connect the other inverters to each other in the same way.

4. Terminate in the last inverter.

Set the DIP switch for the terminal resistor to ON.

5. Close inverters.

Allocate communication address

Recommendation: Continuous numbering from Solar-Log™, starting from 2 (not 1!).

Setting: Using the inverter operating display

Procedure: Start according to the inverter's instructions