Steca

Steca (larger than 17k)

Connect the inverters to each other

Connect using

a 2-wire shielded data cable and

4-pin Phoenix Contact Connection plug type "M12MS SACC-4SC SH“ (two plugs included with the
inverter).

Where to connect: RS485 sockets on the bottom of the inverter.

The RS485 IN and OUT sockets are each double connections so that the wiring can be continued to the

next inverter.

Procedure

Wiring the data cable to the "Phoenix Contact Type M12MS SACC-4SC SH“ according to the manu-
facturer's instructions.

Insert one plug into the OUT (X14B) socket of inverter 1.

Insert the other end of the wire into the IN socket (X15B) on inverter 2.

Connect the other inverters to each other in the same way.

Terminate in the last inverter.
On the sockets "RS485 OUT" with Phoenix contact type M12MS SACC-4SC SH bridge the connec-
tions PIN1 to PIN2 and PIN3 to PIN4.

Close inverters.

Allocate communication address

Recommendation: Continuous numbering starting with 1.

highest possible address: 31

Set the following parameters on the inverter's operating display:

Press "F1", select

Numerical list

, press "ENTER".

Set parameter number

2000

[password protection],

press "ENTER" twice.

Enter

72555

, press "ENTER"

Set parameter number

0406

, press "ENTER"

Select sub parameter

0406,3

, press "ENTER"

Enter figure for communication

x

[

x

= continuous numbering starting with 1; highest possible address: 31], press "ENTER". 31], press

"ENTER".

After configuring on the display:

Using the installed DC isolating switch turn the inverters on and off briefly so that the settings are
activated.

Set the date and time on the inverter as shown in the inverter instructions.