73 shindengen, 73�1 shindengen – Solare Datensysteme Solar-Log User Manual

Page 212

Advertising
background image

212

Shindengen

Shindengen

73 Shindengen

73�1 Shindengen

Easy Installation

Termination

Addressing

Interface

No

Yes

Yes

RS485

Overview

Integrated interface

Where to connect: Terminal strip inside the inverter

3-pin wiring

Communication address must be allocated.

Installation steps

Switch off the inverters and Solar-Log™

Connect inverters to the Solar-Log™

Connect the inverters to each other

Allocate communication address

Connect inverters to the Solar-Log™

The wiring is done using a

self-made, shielded 3 wire data cable with a terminal block connector.

Procedure

1.

Open the inverter as shown in the inverter’s instructions.

2. If you are fabricating the cable yourself, connect the wires as shown in the following diagram.

Solar-Log™ terminal strip connector

Terminal strip inside the inverter

Terminal

RS485 terminal

► 1 A/Data+

► 30 A (+)

► 3 GND

► 31 GND

► 4 B/Data-

► 13 B (-)

3. If only one inverter is to be connected terminate this in accordance with the inverter instructions.

4. Close inverters.

5. Insert the terminal block connector into the Solar-Log™ RS485 socket.

Connect the inverters to each other

Where to connect: Terminal strip inside the inverter

3-pin wiring