Easy Installation

Termination

Addressing

Interface

No

DIP switch

Yes

RS485

Overview

Integrated interface

Where to connect: Terminal strip inside the inverter

3-pin wiring

Communication address must be allocated.

Installation steps

Switch off the inverters and Solar-Log™

Connect inverters to the Solar-Log™

Connect the inverters to each other

Allocate communication address

Connect inverters to the Solar-Log™

The wiring is done using a

self-made, shielded 3 wire data cable with a terminal block connector.

Procedure

1.

Get access to the inverter interface.

2. If you are making the cable yourself, connect the wires as shown in the following diagram:

Solar-Log™ terminal strip connector

Terminal strip inside the inverter

Terminal

RS485 terminal

► 1

► 1 A (Data+)

► 3

► 6 GND

► 4

► 3 B (Data-)

3. If only one inverter is to be connected this must be terminated.

In the inverter, set the DIP switch S1 for the terminal resistor to ON.

4. Insert the terminal block connector into the Solar-Log™ RS485 socket.