85 sunpower, 85�1 sunpower spr-f-model with fronius comcard – Solare Datensysteme Solar-Log User Manual

Page 262

Advertising
background image

262

Sunpower

Sunpower SPR-F-Model with Fronius ComCard

85 Sunpower

85�1 Sunpower SPR-F-Model with Fronius ComCard

Easy Installation

Termination

Addressing

Interface

Yes

Connection plug
Bridge 4-3 + 5-6

Yes

RS422

Select “Fronius” during the inverter detection

Overview

The Fronius ComCard RS422 interface integrated as an option;
otherwise can be retrofitted using „ComCard retrofit“.

Where to connect: RJ45 socket on the outside of the inverter

4 wire cabling with 6-pin terminal block connector

Communication address must be allocated.

-

Recommendation: Continuous numbering starting with 1.

-

Setting: Using the inverter operating display

-

Procedure: Start according to the inverter‘s instructions

Installation steps

Switch off the inverters and Solar-Log™

(Install Fronius ComCard RS485 interface into the inverter).

Connect inverters to the Solar-Log™

Connect the inverters to each other

Allocate communication address

Installing Fronius ComCard RS485 interface

Procedure

► Install the Fronius ComCard RS485 interface in the inverter in accordance with the interface card ins-

tallation instructions.

Connect inverters to the Solar-Log™

The wiring is done using a

ready-made Fronius data cable (optional extra; not supplied)

or

self-made data cable with RJ45 plug and 6-pin terminal block connector

Caution

Risk of damage to the unit!
The Solar-Log™ also has an RJ45 socket, which must never be connected to the RJ45
socket on the inverter.

► ☻

Only connect inverters via the RS485/422 B-Solar-Log™ interface.