40 Huawei

40�1 Huawei

Easy Installation

Termination

Addressing

Interface

No

Yes

Yes

RS485

Overview

Integrated interface

Where to connect: RJ45 socket on the outside of the inverter

2-pin wiring

Communication address must be allocated.

Installation steps

Switch off the inverters and Solar-Log™

Connect inverters to the Solar-Log™

Connect the inverters to each other

Connect inverters to the Solar-Log™

The wiring is done using a

self-made cable connection with RS485 data cable and terminal block connector.

Procedure

Open the inverter as shown in the inverter's instructions.

Insert the RJ45 plug into RS485-Out socket on the inverter.

If you are making the cable yourself, connect the wires as shown in the following diagram

Address the inverter according to the manufacturer's specifications.
Address range 1 to 247.

If only one inverter is to be connected, it must be terminated according to the manufacturer‘s instruc-

tions.

Close the inverter if no other inverters are to be connected.

Insert the terminal block connector into the Solar-Log™ RS485 socket.

Solar-Log™ terminal strip connector

RJ45 inverter

Terminal

PIN

► 1

1 or 4

► 4

2 or 5

Caution

Risk of damage to the unit!
The Solar-Log™ also has an RJ45 socket, which must never be connected to the RJ45
socket on the inverter.

Only connect inverters via the RS485/422 Solar-Log™ interface(s).