Advanced Energy

Advanced Energy - AE-1

4 Advanced Energy

4�1

Advanced Energy - AE-1

Easy Installation

Termination

Addressing

Interface

No

Switch

Yes

RS485

Select “Steca” during the inverter detection

Overview

Integrated interface

Where to connect: RJ socket, on the outside of the inverter‘s interface card.

2-pin wiring

Communication address must be allocated.

Installation steps

Switch off the inverters and Solar-Log™

Connect inverters to the Solar-Log™

Connect the inverters to each other

Allocate communication address

Connect inverters to the Solar-Log™

The wiring is done using a

ready-made data cable (optional extra; not supplied)

or

self-made RS485 data cable with RJ45 plug and terminal block connector.

Caution

Risk of damage to the unit!
The Solar-Log™ also has an RJ45 socket, which must never be connected to the RJ45
socket on the inverter.

Only connect inverters via the RS485/422 Solar-Log™ interface(s).

Procedure

1.

If you are making the cable yourself, connect the wires as shown in the following diagram:

Solar-Log™ terminal strip connector

RJ45 inverter

Terminal

PIN

► 1

► 1

► 4

► 2

2. Insert the RJ45 plug into any RJ45 socket on the first inverter.

3. If only one inverter is to be connected this must be terminated.

On the inverter insert the connection plug into the free RJ45 socket.

4. Insert the terminal block connector into the Solar-Log™ RS485 socket.