94 valenia, 94�1 valenia – Solare Datensysteme Solar-Log User Manual

Page 285

Advertising
background image

285

Valenia

Valenia

94 Valenia

94�1 Valenia

Easy Installation

Termination

Addressing

Interface

No

Yes

Yes

RS485

Overview

Integrated interface

Where to connect: Terminal strip on internal interface card

3-pin wiring

Communication address must be allocated.

Installation steps

Switch off the inverters and Solar-Log™

Connect inverters to the Solar-Log™

Connect the inverters to each other

Set the address of the inverters.

Connect inverters to the Solar-Log™

The wiring is done using a

self-made 3 pin connection cable and terminal block connector.

Procedure

1.

Open the inverter as shown in the inverter's instructions.

2. If you are making the cable yourself, connect the wires as shown in the following diagram

3. If only one inverter is to be connected, according to the manufacturer's handbook it must be termina-

ted.

4. Set the address for the inverter on the inverter itself.

5. Close the inverter if no other inverters are to be connected.

6. Insert the terminal block connector into the Solar-Log™ RS485 socket.

Solar-Log™ terminal strip connector

Inverter terminal strip

Terminal

PIN

► 1

P

► 3

0 V

► 4

N

Note

The inverter terminal strip's 5V output must not be connected to the Solar-Log™.