6 albatech – Solare Datensysteme Solar-Log User Manual

Page 35

Advertising
background image

35

Albatech

Albatech APL Trifase 15 / 20

6 Albatech

6�1

Albatech APL Trifase 15 / 20

Easy Installation

Termination

Addressing

Interface

No

Jumper

Yes

RS485

Inverters from different Albatech model ranges (APL monophase / triphase) cannot be mixed on an RS485

connection. The correct range must be selected when selecting inverters.

Overview

Integrated interface

Where to connect: Terminal strip inside the inverter

3-pin wiring

Communication address must be allocated.

Installation steps

Allocate communication address

Switch off the inverters and Solar-Log™

Connect inverters to the Solar-Log™

Connect the inverters to each other

Note:

If more than 32 inverters are connected a signal amplifier must be installed in the RS485
bus in accordance with the manufacturer.

Connect inverters to the Solar-Log™

The wiring is done using a

self-made, shielded 3 wire data cable and terminal block connector.

It is connected to the inverter as shown in the following diagram. The inverters are terminated on pin 9/10

of J1. Both the first and also the last inverter must be terminated.

Figure 13: Albatech APL block connector