50 mitsubishi – Solare Datensysteme Solar-Log User Manual

Page 151

Advertising
background image

151

Mitsubishi

Mitsubishi with RS485 interface

50 Mitsubishi

50�1 Mitsubishi with RS485 interface

Easy Installation

Termination

Addressing

Interface

No

Switch

Yes

RS485

Overview

Integrated interface

Where to connect: 2 RJ11 sockets inside the inverter.

2-pin wiring

Communication address must be allocated.

Installation steps

Switch off the inverters and Solar-Log™

Connect inverters to the Solar-Log™

Connect the inverters to each other

Allocate communication address

Connect inverters to the Solar-Log™

The wiring is done using a

ready-made RJ11 data cable (optional extra; not supplied)

or

self-made cable connection with RJ11 cable connection and terminal block connector.

Procedure

1.

Unscrew the front plate of the inverter as shown in the inverter's instructions.

2. If you are making the cable yourself, connect the wires as shown in the following diagram:

Solar-Log™ terminal strip connector

RJ11 Inverter

Terminal

PIN

► 1

► 3

► 4

► 4

3. Insert the RJ1plug into any RJ11 socket on inverter 1.

4. If only one inverter is to be connected this must be terminated.

In the inverter, set the DIP switch for the terminal resistor to ON.

5. Screw the front plate inverter on again if no other inverters are to be connected.

6. Insert the terminal block connector into the Solar-Log™ RS485 socket.

Connect the inverters to each other

Connect using a data cable with an RJ11 plug.

Where to connect: 2 RJ11 sockets at the bottom left inside the inverter.