Solare Datensysteme Solar-Log User Manual

Page 201

Advertising
background image

201

Schneider Electric

Schneider Electric Xantrex GT30E

71�2 Schneider Electric Xantrex GT30E

Easy Installation

Termination

Addressing

Interface

No

-

No

Sub D9 socket

Overview

Integrated interface

Where to connect: Sub D 9 socket X51 inside the inverter.

2-pin wiring

Communication address must be allocated to the inverter.

Installation steps

Switch off the inverters and Solar-Log™

Connect inverters to the Solar-Log™

Connect the inverters to each other


Connect inverters to the Solar-Log™

The wiring is done using a

ready-made data cable (optional extra; not supplied)

self-made, shielded 2 wire data cable and terminal block connector

Procedure:

1.

Open the inverter as shown in the inverter's instructions.

2. If you are making the cable yourself, connect the wires as shown in the following diagram

Solar-Log™ terminal strip connector

Inverters

RS485 A

Sub D9 socket X51

► 1

► 8

► 4

► 6

3. Close the inverter if no other inverters are to be connected.

4. Insert the terminal block connector into the Solar-Log™ RS485 socket.

Connect the inverters to each other

Connect using a 2 wire, shielded data cable

Where to connect: Sub D 9 socket X51 inside the inverter.

Procedure

1.

If you are making the cable yourself, connect the wires as shown in the following diagram

Solar-Log™ terminal strip connector

Inverters

RS485/422 B

Sub D9 socket X51

► 1

► 8

► 4

► 6

2. Connect the other inverters to each other in the same way (1:1).

3. Close the inverter if no other inverters are to be connected.

4. Insert the terminal block connector into the Solar-Log™ RS485 socket.