Solare Datensysteme Solar-Log User Manual

Page 131

Advertising
background image

131

Ingeteam

Ingeteam

Connect the inverters to each other

Connect using a 3 wire, shielded data cable

Where to connect: Terminal strip inside the inverter (on the retrofitted RS485 interface)

Procedure

1.

Open the inverter as shown in the inverter's instructions.

2. Connect terminals "Pin 1-RS485-A (+)", "Pin 6-GND" and "Pin 2-RS485-B (-)" of inverter 1 to the corre-

sponding terminals on inverter 2.

3. Connect the other inverters to each other in the same way.

4. Terminate in the last inverter.

Insert jumper JP3 into the RS485 card.

5. Close inverters.

Allocate communication address

Recommendation: Continuous numbering starting with 1.

Setting: Using the inverter operating display

Procedure: Start according to the inverter's instructions