Solare Datensysteme Solar-Log User Manual

Page 258

Advertising
background image

258

Steca

Steca (larger than 17k)

83�2 Steca (larger than 17k)

Easy Installation

Termination

Addressing

Interface

No

Yes

Yes

RS485

Overview

Integrated interface

Where to connect: RJ45 socket on the bottom of the inverter

2-pin wiring

Communication address must be allocated.

Installation steps

Switch off the inverters and Solar-Log™

Connect inverters to the Solar-Log™

Connect the inverters to each other

Select the Steca >=17k inverter during the initial configuration.

Note

To use active and reactive power management, all of the inverters need to be set to:

Protocol 1

57600 baud

Parameter 1164 = 2

Connect inverters to the Solar-Log™

The wiring is done using a

self-made, shielded 2 wire data cable and terminal block connector.

Procedure

Connect wires as shown in the diagram below.

Solar-Log™ terminal strip connector

RS485 inverter socket

Terminal

PIN

► 1

► 2

► 4

► 3

If only one inverter is to be connected this must be terminated.
On the sockets "RS485 OUT" with SACC-M12MS-4SC round plugs bypass the connections PIN1 to
PIN2 and PIN3 to PIN4.

Close the inverter if no other inverters are to be connected.

Insert the terminal block connector into the Solar-Log™ RS485 socket.