Platinum (formerly Diehl Ako)

Platinum with RS485 interface

58 Platinum (formerly Diehl Ako)

58�1 Platinum with RS485 interface

Easy Installation

Termination

Addressing

Interface

Yes

Yes

No

RS485

Overview

Integrated interface

Where to connect: RJ45 socket on the bottom of the inverter

2-pin wiring

Communication address does not have to be assigned

Note

The order in which the inverters are displayed in the Solar-Log™ after detection is random.
We strongly recommend that you change the order of the inverters immediately after de-
tection at startup, in the

Configuration/Basis/Inverters

dialog box.

The inverters can be identified using the displayed serial number.

Installation steps

Switch off the inverters and Solar-Log™

Connect inverters to the Solar-Log™

Connect the inverters to each other

Connect inverters to the Solar-Log™

The wiring is done using a

ready-made data cable (optional extra; not supplied)

or

self-made cable connection with RS485 data cable and terminal block connector.

Procedure

1.

If you are making the cable yourself, connect the wires as shown in the following diagram:

Solar-Log™ terminal strip connector

RJ45 inverter

Terminal

PIN

► 1

► PIN 6 (A)

► 4

► PIN 3 (B)

2. Insert the RJ45 plug into the RJ45 socket on the inverter.

3. If only one inverter is to be connected terminate this in accordance with the inverter instructions.

4. Insert the terminal block connector into the Solar-Log™ RS485 socket.