58�2 platinum h – Solare Datensysteme Solar-Log User Manual

Page 169

Advertising
background image

169

Platinum (formerly Diehl Ako)

Platinum H

58�2 Platinum H

Easy Installation

Termination

Addressing

Interface

No

Yes

Yes

RS485

Overview

Integrated interface

Where to connect: Terminal strip inside the inverter

2-pin wiring

Communication address must be allocated.

Installation steps

Switch off the inverters and Solar-Log™

Connect inverters to the Solar-Log™

Connect the inverters to each other

Configure the inverter’s communication interface

Allocate communication address

Connect inverters to the Solar-Log™

The wiring is done using a

self-made, shielded 2 wire data cable and terminal block connector.

Procedure

1.

Connect wires as shown in the diagram below.

Solar-Log™ terminal strip connector

Inverter terminal strip

Terminal

Terminal

► 1

► B (Data +)

► 4

► A (Data -)

2. If only one inverter is to be connected, it must be terminated according to the manufacturer’s instruc-

tions.

3. Close the inverter cover if no other inverters are to be connected.

4. Insert the terminal block connector into the Solar-Log™ RS485 socket.

Connect the inverters to each other

The inverters are connected together using

the RS485 interface. Refer to the manufacturer’s inverter manual for the details on how to setup the con-

nection.

Allocate communication address

Recommendation: Continuous numbering starting with 1.

Setting: Using the inverter operating display

Procedure: Start according to the inverter’s instructions