Solare Datensysteme Solar-Log User Manual

Page 128

Advertising
background image

128

Hyundai

Hyundai HPC-250HT-E

41�2 Hyundai HPC-250HT-E

Easy Installation

Termination

Addressing

Interface

No

Yes

Yes

RS485

Overview

Integrated interface

Where to connect: 20 pin connection strip on the outside of the inverter at the top edge of the
i-8142iW module.

2-pin wiring

Communication address must be allocated.

Installation steps

Switch off the inverters and Solar-Log™

Connect inverters to the Solar-Log™

Connect the inverters to each other

Allocate communication address

Connect inverters to the Solar-Log™

The wiring is done using a

ready-made data cable (optional extra; not supplied)

or

self-made, shielded 2 wire data cable and terminal block connector.

Caution

Risk of damage to the unit!
The Solar-Log™ also has an RJ45 socket, which must never be connected to the RJ45
socket on the inverter.

Only connect inverters via the RS485/422 Solar-Log™ interface(s).

Procedure

1.

If you are making the cable yourself, connect the wires as shown in the following diagram:

Solar-Log™ terminal strip connector

Inverter terminal strip

Terminal

Terminal

► 1

► D1+/TxD1+

► 4

► D1-/TxD1-

2. If only one inverter is to be connected terminate this in accordance with the inverter instructions.

3. Insert the terminal block connector into the Solar-Log™ RS485 socket.

Connect the inverters to each other

Connect using a 2 wire, shielded data cable

Where to connect: 20 pin connection strip on the inverter at the top edge of the i-8142iW module.